EVEMS Safety Current: An Essential Technical Requirement
July 2, 2025
11 minutes

Transportation electrification is progressing rapidly in Quebec and Canada. Electric Vehicle Energy Management Systems (EVEMS) represent an effective solution for optimizing the use of electrical infrastructure. However, confusion remains regarding their dimensioning (i.e., establishing the necessary electrical capacity), particularly with regard to the role of safety current.
Key Takeaway
Important: The safety current of charging stations (EVSE) must be included in your load calculations. Section 8-106(11) of the Canadian Electrical Code allows charging stations to be excluded from load calculations only when the EVEMS actively monitors and controls them. In the event of a failure, this exception no longer applies.
The only exception is if the EVEMS manufacturer guarantees in writing a safety current of 0 A for each charging station.
What is safety current?
The safety current is the maximum current that a charging station can draw in the event of an EVEMS failure. This value is predefined by the manufacturer and becomes active when the charging station loses communication with the EVEMS or if the system enters failure mode.
Note: This is not necessarily the charging station’s rated current. It is the “default” load in the event of a problem.
Principle of EVEMS and safety current
Normal operation of an EVEMS involves smart distribution of the available power between several charging stations. However, in the event of a system failure, each charging station reverts to its safety current, and it is this value that must be taken into account when dimensioning the installation.
Practical example
Consider a 12-unit building:
- 400A main service
- 12 charging stations installed
- Rated current = 32A per charging station
- Safety current = 8A per charging station
- Total safety current = 96A
Scenario 1: The annual peak is unknown
If you do not know the annual peak consumption of the 400A service, you cannot use an EVEMS to monitor the main input and control the charging stations, since you cannot guarantee that the 400A input will have the residual capacity necessary to accommodate the 96A of safety current from the 12 charging stations if the EVEMS fails.
Scenario 2: The annual peak is known
Even if you know the annual peak, you can only use an EVEMS if this peak is less than 304A (400A – 96A), or 224A if the maximum usage rule of 80% (320A – 96A) applies.
Detailed calculation:
- Maximum available capacity = 400A
- Minimum safety current to be guaranteed = 96A
- Maximum annual peak allowed = 400A – 96A = 304A
If the maximum usage rule of 80% is applied (recommended for continuous loads such as electric vehicle supply equipment or EVSE):
- Available capacity = 400A * 80% = 320A
- Maximum annual peak (with 80%) = 320A – 96A = 224A
Solution for special cases
The only way to use an EVEMS without knowing the annual peak, or when it is too high, is for the EVEMS manufacturer to guarantee in writing that the safety current is 0A for each charging station.
This means that the manufacturer guarantees that its charging stations will completely stop consuming power in the event of a failure. Without this formal written guarantee, you must include the total safety current in your load calculation.
Interpretation of the Canadian Electrical Code
Fundamental rule: 8-104(2)
“The calculated load in a circuit shall not exceed the ampere rating of the circuit.”1 [free translation]
This rule applies without exception, including in EVEMS failure scenarios.
Rule 8-106(11) : A conditional exception
“For the purposes of Rules […], where an [EVEMS] as described in Subrule 10) monitors the consumer’s service and feeders and controls the [EVSE] loads in accordance with Rule 8-500, the demand load for the [EVSE] shall not be required to be considered in the determination of the calculated load.”2
This provision allows for the exclusion of certain EVSE charges from the calculation, but only when the EVEMS is functioning normally. The key words are “monitors” and “controls” — actions that cease in the event of a system failure.
A common mistake is to believe that this section applies at all times. As soon as one of these conditions is no longer met—whether due to a failure of monitoring, a loss of control, or a breakdown in communication between system components—the exception in section 8-106(11) no longer applies.
Rule 8-500(2): The responsibility of the EVEMS
“An [EVEMS] shall not cause the load of a branch circuit, feeder, or service to exceed the requirements of Rule 8-104 (5) or (6).”3 [free translation]
This rule emphasizes that design must take into account all conditions, including failure scenarios.
Failure scenarios to consider
Probable failures
- Loss of wireless communication
- Internet outages
- Problematic software updates
- Software bugs
Possible failures
- Physical damage to equipment
- Hacking of EVEMS software
- Controllers hardware failure
These scenarios are part of the operational reality of complex systems and must be taken into account to ensure their safe installation.
Why is this important?
Neglecting the safety current by relying on exception 8-106(11) may expose the installation to:
- Overloads: tripping of main circuit breakers, service interruptions
- Overheating: damage to cables, connections, transformers
- Fire hazards: potential consequence of prolonged overload
- Non-compliance with the Code: refusal of installation during inspection, legal liability in the event of an incident
What this means for professionals
For electricians and installers
- Ask for the safety current value before installation
- Check that the existing infrastructure can handle the total safety current in addition to the peak load or confirm the written 0 A guarantee
- Document the calculations and the presence (or absence) of the guarantee for inspections
For engineers and designers
- Include safety current in load calculations unless a written guarantee of 0 A is provided and deemed acceptable
- Clearly specify capacity requirements in plans and specifications
For inspectors
- Check that the safety current has been taken into account in the calculations or that a formal written guarantee of 0 A is provided by the manufacturer
- Request documentation from the manufacturer regarding safety currents if not provided
- Make sure that the infrastructure can handle the total potential load, including the safety current in case of failure
The solution: Dimensioning including safety current
To ensure safety and compliance with the Code, professionals must:
- Identify the safety current for each charging station
- Calculate the total safety currents for all charging stations
- Dimension the entire infrastructure to support this potential load
- Provide a dedicated power supply for the total safety currents
- Obtain a written guarantee of 0 A safety current if necessary
Frequently asked questions
No. An EVEMS may lose its control capability (current limitation) while continuing to monitor, or lose communication. Monitoring without control does not provide protection. The fail-safe mode (safety current) is what determines the load if control is lost.
Electrical safety according to the Code is based on protection against all reasonably foreseeable failure scenarios to ensure the protection of people and property in all circumstances. A loss of communication or software/hardware failure is foreseeable.
Only when the EVEMS is functioning normally, actively monitoring and controlling loads without failure. As soon as any of these conditions is no longer met, the exception no longer applies and the safety current must be taken into account.
This information should be available in the technical documentation provided by the EVSE manufacturer or obtained directly from the manufacturer. If the manufacturer guarantees a safety current of 0 A in writing, this document is essential.
Conclusion
Taking safety current into account is an essential requirement for Code compliance and installation safety. Professionals must either properly dimension the infrastructure to support the total safety current or obtain a written guarantee from the manufacturer that the safety current is zero.
Safety current is a fundamental requirement of the Canadian Electrical Code to ensure safety even in the event of a failure of smart management systems. It is our professional responsibility to strictly apply the Code to protect people and property.